| Model |
MPS 8000 |
| Rating |
8 KVA |
| AC INPUT |
415V + 15% -20% Three Phase Input |
| Frequency |
50Hz ± 6% |
| DC VOLTAGE: |
180 VDC |
| Charging Time |
12 Hours for 90% of full Capacity |
| Charger Type |
CVCC Internal Controlled Rectifier type |
| |
| INVERTER: |
| Technology |
IGBT Double Conversion |
| Output Voltage |
400 / 415V AC Three Phase |
| Frequency |
50Hz ± 0.5Hz |
| Waveform |
PWM Sine wave |
| Harmonic Distortion |
Less than 3% on Linear Load |
| Inverter Efficiency |
> 90% |
| Power Factor |
0.8 |
| Overload |
105% Continuous, 300% for 60 sec |
| Crest Factor |
4:1 |
| Phase Displacement |
1200 ± 10 |
| Audible Noise |
Less than 45 dB at 1 Meter |
| |
| METERING: |
| Microprocessor based Digital LCD Meter for |
R,Y,B Output Voltages, Output currents & Frequency, DC Voltage , Battery and Load Percentage, Last 5 Backup time Storage with no. of Lift Operation per Backup. |
| |
| GENERAL: |
| Dimensions (LxWxH)mm |
740x 350 x 800 |
| Operating temperature |
00C to 500C |
| Humidity |
Max 95%, Non-condensing |
| |
| PROTECTIONS : |
| Output Overload & Short circuit, Output Under & Overvoltage, DC Under & Overvoltage Input Under & Overvoltage, Single Phasing & Phase unbalance |
| |
| INDICATIONS & ALARMS |
| a) Mains on |
Indication |
| b) Inverter on |
Indication |
| c) DC Low |
Indication & Alarm |
| d) fault |
Indication & Alarm |
| e) Output Overload |
Indication & Alarm |
| |
| CHANGE-OVER |
a) Electro mechanical switch Internal for single lift, External for Multiple Lifts
b) Static Switch Bi-directional optional |
| |
| * Specifications are subject to change without prior notice due to constant improvement in design & technology |