Product
Online UPS Systems > Maxima Series > 10 KVA
 
 
TECHNICAL SPECIFICATIONS FOR ONLINE UPS 3Ph to 3Ph – Maxima Series
 
Model MPS 10
Rating 10 KVA
AC INPUT 415V + 15%  -20%  Three Phase Input
Frequency 50Hz  ± 6%
DC  VOLTAGE: 360VDC                    
Charging Time 12 Hours for 90% of full Capacity
Charger Type CVCC  Internal Controlled Rectifier type
 
INVERTER:
Technology IGBT Double Conversion
Output Voltage 400V  AC Three Phase
Voltage Regulation ± 1% for DC I/p variation  & o/p load  variation
Frequency 50Hz ± 0.05Hz
Waveform PWM Sine wave
Harmonic Distortion Less than 3%
Inverter Efficiency > 92%
Power Factor 0.8
Overload  150% for 60 sec
Crest Factor 3:1
Transient Recovery ± 4% under full load change and corrected within 60msec
Phase Displacement 1200 ± 10
Audible Noise Less than 50 dB at 1 Meter
 
METERING:
Microprocessor based Digital LCD Meter for R,Y,B Output Voltage, Output current & Frequency, DC Voltage , Battery and Load Percentage
 
GENERAL:
Dimensions (LxWxH)mm 1040 x 350 x 910
Operating temperature 00C to 500C
Humidity Max 95%, Non-condensing
 
PROTECTIONS :
Output Overload  & Short circuit, Output Under & Overvoltage, DC Under & Overvoltage  Input Under & Overvoltage, Single Phasing & Phase unbalance
 
INDICATIONS & ALARMS
a) Mains on Indication
b) Inverter on Indication
c) DC Low Indication & Alarm
d) fault Indication & Alarm
e) Output Overload Indication & Alarm
 
BYPASS FACILITY
Static Bypass Switch(Optional) Bi-directional
   
* Specifications are subject to change without prior notice due to constant improvement in design & technology
 
 

 

About us | Product | Process & Quality | Clients | Client Testimonials | Downloads | Enquiry | Contact Us