| Model |
MPS 03 |
| Rating |
3 KVA |
| AC INPUT |
230V + 15% -20% Single Phase Input |
| Frequency |
50Hz ± 6% |
| DC VOLTAGE: |
144 VDC |
| Charging
Time |
12 Hours for 90% of full Capacity |
| Charger
Type |
CVCC Internal Controlled Rectifier type |
| |
| INVERTER: |
| Technology |
IGBT Double
Conversion |
| Output
Voltage |
230V AC Single Phase |
| Voltage
Regulation |
± 1% for DC I/p variation & o/p load variation |
| Frequency |
50Hz ± 0.05Hz |
| Waveform |
PWM Sine wave |
| Harmonic
Distortion |
Less
than 3% |
| Inverter
Efficiency |
>
90% |
| Power
Factor |
0.8 |
| Overload |
150% for 60 sec |
| Crest
Factor |
3:1 |
| Transient
Recovery |
± 4% under full load change and corrected within 60msec |
| Audible
Noise |
Less than 45 dB at 1 Meter |
| |
| METERING: |
| Microprocessor based Digital LCD Meter for |
Output Voltage, Output current & Frequency, DC Voltage & Current, Battery and Load Percentage |
| |
| GENERAL: |
| Dimensions
(LxWxH)mm |
640x 240x 500 |
| Operating
temperature |
00C to
500C |
| Humidity |
Max 95%,
Non-condensing |
| |
| PROTECTIONS : |
| Output Overload & Short circuit, Output Under & Overvoltage, DC Under & Overvoltage Input Under & Overvoltage, Single Phasing & Phase unbalance |
| |
| INDICATIONS
& ALARMS |
| a) Mains on |
Indication |
| b) Inverter on |
Indication |
| c) DC Low |
Indication & Alarm |
| d) fault |
Indication & Alarm |
| e) Output Overload |
Indication & Alarm |
| f) Mains fail |
Indication & Alarm |
| |
| BYPASS
FACILITY |
| a) Manual Bypass Switch |
Provided as Standard feature |
| Static Bypass Switch(Optional) |
Bi-directional |
| |
|
| * Specifications are subject to change without prior notice due to constant improvement in design & technology |