Megatech Turbo Series Power Factor corrected 3-Ph Online UPS-200KVA
|
I) Input
|
Voltage
|
415V, 3 Phase, 4 Wire
|
|
Voltage variation
|
320V to 475V
|
|
Frequency
|
50Hz nominal
|
|
Frequency variation
|
± 6%
|
|
Input Current THD
|
Better than 5% with Active IPM based front-end converter at full load with grid
voltage harmonics less than 2%
|
|
Power Factor
|
Near Unity with IGBT based Active front-end converter at UPS input.
|
|
Efficiency Overall
|
Better than 88% from 50% to 100% of output load.
|
|
|
|
II) Output
|
Voltage
|
415V, 3 phase, 4 wire
|
|
Voltage distortion
|
Less than 3% with linear load.
|
|
|
Less than 5% with non-linear load.
|
|
Voltage Variation
|
± 1% for static balanced load
|
|
|
± 10% for unbalanced load
|
|
Rated Load KVA
|
200KVA /160KW
|
|
Overload
|
110% for 10 min., 150% for 1 min.
|
|
Output frequency
|
"50Hz (mains synchronized) +/- 6%+/- 0.1% free running "
|
|
|
|
III) Static Bypass
|
I) Inverter to Bypass
|
|
a) Inverter Overload
|
Over lapped transfer
|
|
b) Manual Command
|
Over lapped transfer
|
|
c) Inverter failure
|
< 2 ms in sync mode
|
|
II) Bypass to inverter auto &manual
|
Over lapped transfer
|
|
|
|
IV) Battery
|
Battery Voltage
|
360 /384 /480V
|
|
Charging Mode
|
Constant Current Constant Voltage
|
|
Charging Voltage
|
2.25V per Cell
|
|
Battery Charger Rating
|
Maximum 10A ( Higher capacity Charger available on request)
|
|
|
|
V) Environment Conditions
|
Operating temperature
|
0 – 40°C for guaranteed performance
|
|
Audible Noise
|
< 60 dBA.
|
|
Cooling
|
Forced air-cooling.
|
|
|
|
VI) Protections
- Input under voltage
- Input over voltage
- Output under voltage
- Output over voltage
- Battery over charging
- Input in rush current protection by soft start as well as pre-charge circuitry
- Output over load
- Battery Under voltage
- DC Over voltage
- Output Short circuit
|
|
|
VII)
1) Metering
- Input voltage
- Input current
- Output voltage
- Output current
- Battery voltage
- Battery current
- Output frequency
- Input frequency
- Faults
|
2) Status indications
- Input Converter ON
- Inverter ON
- Static switch on Mains / Inverter.
- Battery ON
|
3) User operated controls
- System ON / OFF.
- Display mode selection.
- Reset
|
4) Networking & Monitoring interface
- RS 232.
- SNMP ( optional at additional cost )
|
|
|
VIII) Paralleling (Optional)
|
Number of systems that can be paralleled
|
Maximum Two.
|
|
Load Current sharing
|
Load current will be equally shared with +/- 5% tolerance at full load.
|
* R & D being continuous process specifications are subject to change
|
|
|