Turbo Online UPS 120KVA
Megatech Turbo Series Power Factor corrected 3-Ph Online UPS-120KVA

I) Input

Voltage 415V, 3 Phase, 4 Wire
Voltage variation 320V to 475V
Frequency 50Hz nominal
Frequency variation ± 6%
Input Current THD Better than 5% with Active IPM based front-end converter at full load with grid voltage harmonics less than 2%
Power Factor Near Unity with IGBT based Active front-end converter at UPS input.
Efficiency Overall Better than 88% from 50% to 100% of output load.
 

II) Output

Voltage 415V, 3 phase, 4 wire
Voltage distortion Less than 3% with linear load.
Less than 5% with non-linear load.
Voltage Variation ± 1% for static balanced load
± 10% for unbalanced load
Rated Load KVA 120KVA /100KW
Overload 110% for 10 min., 150% for 1 min.
Output frequency "50Hz (mains synchronized) +/- 6%+/- 0.1% free running "
 

III) Static Bypass

I) Inverter to Bypass
a) Inverter Overload Over lapped transfer
b) Manual Command Over lapped transfer
c) Inverter failure < 2 ms in sync mode
II) Bypass to inverter auto &manual Over lapped transfer
 

IV) Battery

Battery Voltage 360 /384
Charging Mode Constant Current Constant Voltage
Charging Voltage 2.25V per Cell
Battery Charger Rating Maximum 10A ( Higher capacity Charger available on request)
 

V) Environment Conditions

Operating temperature 0 – 40°C for guaranteed performance
Audible Noise < 60 dBA.
Cooling Forced air-cooling.
 

VI) Protections

  • Input under voltage
  • Input over voltage
  • Output under voltage
  • Output over voltage
  • Battery over charging
  • Input in rush current protection by soft start as well as pre-charge circuitry
  • Output over load
  • Battery Under voltage
  • DC Over voltage
  • Output Short circuit
 

VII)

1) Metering
  • Input voltage
  • Input current
  • Output voltage
  • Output current
  • Battery voltage
  • Battery current
  • Output frequency
  • Input frequency
  • Faults
2) Status indications
  • Input Converter ON
  • Inverter ON
  • Static switch on Mains / Inverter.
  • Battery ON
3) User operated controls
  • System ON / OFF.
  • Display mode selection.
  • Reset
4) Networking & Monitoring interface
  • RS 232.
  • SNMP ( optional at additional cost )
 

VIII) Paralleling (Optional)

Number of systems that can be paralleled Maximum Two.
Load Current sharing Load current will be equally shared with +/- 5% tolerance at full load.
* R & D being continuous process specifications are subject to change